Home > Products >
Description
- Rated temperature : 105℃
- Rated voltage : 300V
- Reference standard : UL Subject 758, UL 1581 & CSA C22.2 No. 210, IEC60754-2
- Silver plated, tinned or bare or silver plated, stranded or solid copper conductor, 40-10 AWG
- Crosslinked FRPE insulation
- Uniform insulation thickness to ensure easy stripping and cutting
- Passes UL VW-1 & CSA FT1 verticla flame test
Application
- For internal wiring of electronic and electrical equipment
- can substitute UL1061
 
Part No. Conductor
AWG
Conductor
No./mm
Conductor
Dia./mm
Insulation
Nom.
Thick/mm
Insulation
Nom.
Dia./mm
Maximum
Resistance at
20℃(Ω/km)
127101 26 7/0.16 0.48 0.26 1.00 139
127102 24 11/0.16 0.61 0.26 1.13 88.9
127104 22 17/0.16 0.76 0.26 1.28 57.5
127106 20 26/0.16 0.94 0.26 1.46 34.6
127108 18 16/0.254 1.16 0.26 1.68 23.3
127109 17 42/0.18 1.34 0.26 1.86 17.4
127110 16 26/0.254 1.49 0.26 2.01 15.1
127112 14 41/0.254 1.87 0.26 2.39 9.2
127113 12 65/0.254 2.36 0.26 2.88 5.4
127114 10 66/0.32 3.00 0.26 3.52 4.1
* Please click on the part numbers for downloading cable specifications.
Both Chinese and English versions are available.